LX3V
Entry level PLC, expandable through expansion modules and BD modules. Optional Ethernet port.
LX5S
Mid-range PLC expandable through expansion modules and BD modules. Integrated motion functions. Integrated Ethernet port.
Model | LX3V Series AC / DC (Transistor) |
---|---|
Power Supply | 85~265 VAC 50 ~ 60Hz / 24 VDC ±10% |
Power Outage Time | 10 ms |
Power Fuse | 250 V 3.15A |
Rush Current | <15 A 5 ms / 100 VAC; <30 A 5 ms / 200 VAC; <15 A 1 ms / 24 VDC |
Power Consumption | <35 W (AC) ; <30 W (DC) |
Power Output | 24 VDC 850 mA |
Running Mode | Round Scan/ Interrupt |
Programming | Instruction List/ Ladder |
Total Instructions | Basic Instructions: 27 / Applied Instruction: 138 |
Execute time | Basic Instructions: 0.06 us / Applied Instruction: 1 ~ 10 us |
System Storage | 16K |
Download/ Monitoring | Serial Programming Cable / Mini USB |
High Speed Pulse | Transistor: 2 channels (4 channel optional) / Relay N/A (2 channel optional) |
External Interrupt | 6 Channels |
Timer Interrupt | 3 Channels |
Holding Addresses | Adjustable |
Filter | For all X input terminals |
Serial Port | COM1: RS422 or RS485 COM2: RS485 |
Temperature | Working Temperature: 0 + 55℃ / Storage Temperature: -20 + 70℃ |
Humidity | 5~ 85% RH (Without condensation) |
Shock Resistance | JIS C 0040 Standard |
Influence Immunity | Meet the IEC61000-4-4 and GB/T 17626.4 standard. Noise voltage amplitude 1 KVP-P, pulse width 10 us, period 0.3 s, edge time 5 ns, duration 1 min. |
Output Mode | Transistor |
Input Power Supply | 24 VDC |
Output Circuit | 5 ~ 30 VDC |
COM Port Current | <0.1 mA (30 VDC) |
Insulation | Optical Coupling |
Leak current | 0.1 mA / 30 VDC |
Min. Load | 5 VDC 2 mA |
Max. Load Resistive | 0.5 A point 0.8 A COM port 0.3 A HSPO point |
Max. Load Inductive | 12 W / 24 VDC 7.2 W HSPO point |
Max. Load Genral | 0.9 W / 24 VDC |
Response Time | <0.2 ms (Pulse output terminal: <5 us) |
CE | YES |
Model | LX5S (08-06 / 12-08) Series AC / DC (Transistor) |
---|---|
Power Supply | 85~265 VAC 50 ~ 60Hz / 24 VDC ±10% |
Power Outage Time | 10 ms |
Power Fuse | 250V 3.15A |
Rush Current | <15 A 5 ms / 100 VAC; <30 A 5 ms / 200 VAC ; <15 A 1 ms / 24 VDC |
Power Consumption | <35 W (AC) ; <30 W (DC) |
Power Output | 24 VDC 850 mA |
Running Mode | Round Scan/ Interrupt |
Programming | Instruction List/ Ladder |
Total Instructions | Basic Instructions: 29 / Applied Instruction: 170 |
Execute time | Basic instruction 0.03-0.008 µS |
System Storage | 512 K |
Download/ Monitoring | Serial Programming Cable / Mini USB |
High Speed Pulse Output | Transistor type; 2 channels/200KHz |
High Speed Counter Interrupt | 100 |
Timer Interrupt | 100 channels, support 0.1 ms interrup |
External Input Interrupt | X0-X5 supports both rising and falling edges |
High Speed Input Single Phase | 2 channels 150 KHz ; 4 channels 10 KHz |
High Speed Input AB Phase | 1 channel 100 KHz, supports 2 or 4 frequency multiplication 2 channels 100 KHz, supports 2 or 4 frequency multiplication |
Power Down Save | Adjustable by software |
Filter | For all X input terminals |
Serial Port | COM1: RS422 COM2: RS485 |
Ethernet Port | BD Board needed |
Temperature | Working Temperature: 0 + 55℃ / Storage Temperature: -20 + 70℃ |
Humidity | 5~ 85% RH (Without condensation) |
Shock Resistance | JIS C 0040 Standard |
Influence Immunity | Meet the IEC61000-4-4 and GB/T 17626.4 standard. Noise voltage amplitude 1 KVP-P, pulse width 10 us, period 0.3 s, edge time 5 ns, duration 1 min. |
Output Mode | Transistor |
Input Power Supply | 24 VDC |
Output Circuit | 5 ~ 30 VDC |
COM Port Current | <0.1 mA (30 VDC) |
Insulation | Optical Coupling |
Leak current | 0.1 mA / 30 VDC |
Min. Load | 5 VDC 2 mA |
Max. Load Resistive | 0.5 A point 0.8 A COM port 0.3 A HSPO point |
Max. Load Inductive | 12 W / 24 VDC 7.2 W HSPO point |
Max. Load Genral | 0.9 W / 24 VDC |
Response Time | <0.2 ms (Pulse output terminal: <5 us) |
CE | YES |
Model | LX5S (12-12 / 14-12) Series AC / DC |
---|---|
Power Supply | 85~265 VAC 50 ~ 60Hz / 24 VDC ±10% |
Power Outage Time | 10 ms |
Power Fuse | 250V 3.15A |
Rush Current | <15 A 5 ms / 100 VAC; <30 A 5 ms / 200 VAC |
Power Consumption | <60 W |
Power Output | 24 VDC 700 mA |
Running Mode | Round Scan/ Interrupt |
Programming | Instruction List/ Ladder |
Total Instructions | Basic Instructions: 27 / Applied Instruction: 170 |
Execute time | Basic Instructions: 0.01 us ~ 0.03 us |
System Storage | 512 KB |
Download/ Monitoring | Serial Programming Cable / Mini USB |
High Speed Pulse Output | Transistor: 4 channels / 200 K |
High Speed Counter Interrupt | 100 Channels |
Timer Interrupt | 100 Channels, Interruption time (min): 0.1ms |
External input interrupt | 0-X7 supports both rising and falling edges |
High Speed Input Single | 4 Channels 150KHz |
High Speed Input AB Phase | 4 channels 100KHz, frequency modes:1/2/4 times |
Power Down save | Adjustable by software |
Filter | For all X input terminals |
Serial Port | COM1: RS422 or RS485 COM2: RS485 |
Ethernet Port | 1 x 10/100 Mbps |
Temperature | Working Temperature: 0 + 55℃ / Storage Temperature: -20 + 70℃ |
Humidity | 5~ 85% RH (Without condensation) |
Shock Resistance | JIS C 0040 Standard |
Influence Immunity | Meet the IEC61000-4-4 and GB/T 17626.4 standard. Noise voltage amplitude 1 KVP-P, pulse width 10 us, period 0.3 s, edge time 5 ns, duration 1 min. |
Output Mode | Transistor |
USB Supply | Use for upgrading firmware, downloading ladder diagram |
Input Power Supply | 24 VDC |
Output Circuit | 5 ~ 30 VDC |
COM Port Current | <0.1 mA (30 VDC) |
Insulation | Optical Coupling |
Leak current | 0.1 mA / 30 VDC |
Min. Load | 5 VDC 2 mA |
Max. Load Resistive | 0.5 A point 0.8 A COM port 0.3 A HSPO point |
Max. Load Inductive | 12 W / 24 VDC 7.2 W HSPO point |
Max. Load Genral | 0.9 W / 24 VDC |
Response Time | <0.2 ms (Pulse output terminal: <5 us) |
CE | YES |
Model | LX5S (24-24 / 36-24) Series AC / DC (Transistor) |
---|---|
Power Supply | 85~265 VAC 50 ~ 60Hz / 24 VDC ±10% |
Power Outage Time | 10 ms |
Power Fuse | 250V 3.15A |
Rush Current | <15 A 5 ms / 100 VAC; <30 A 5 ms / 200 VAC ; <15 A 1 ms / 24 VDC |
Power Consumption | <35 W (AC) ; <30 W (DC) |
Power Output | 24 VDC 850 mA |
Running Mode | Round Scan/ Interrupt |
Programming | Instruction List/ Ladder |
Total Instructions | Basic Instructions: 29 / Applied Instruction: 170 |
Execute time | Basic instruction 0.03-0.008 µS |
System Storage | 512 K |
Download/ Monitoring | Serial Programming Cable / Mini USB |
High Speed Pulse Output | Transistor type; 2 channels/200KHz |
High Speed Counter Interrupt | 100 |
Timer Interrupt | 100 channels, support 0.1 ms interrup |
External Input Interrupt | X0-X5 supports both rising and falling edges |
High Speed Input Single Phase | 6 channels 150 KHz |
High Speed Input AB Phase | 3 channels 100K Hz, supports 2 or 4 frequency multiplication |
Power Down Save | Adjustable by software |
Filter | For all X input terminals |
Serial Port | COM1: RS422 COM2: RS485 |
Ethernet Port | 1 x 10/100 Mbps |
Temperature | Working Temperature: 0 + 55℃ / Storage Temperature: -20 + 70℃ |
Humidity | 5~ 85% RH (Without condensation) |
Shock Resistance | JIS C 0040 Standard |
Influence Immunity | Meet the IEC61000-4-4 and GB/T 17626.4 standard. Noise voltage amplitude 1 KVP-P, pulse width 10 us, period 0.3 s, edge time 5 ns, duration 1 min. |
Output Mode | Transistor |
Input Power Supply | 24 VDC |
Output Circuit | 5 ~ 30 VDC |
COM Port Current | <0.1 mA (30 VDC) |
Insulation | Optical Coupling |
Leak current | 0.1 mA / 30 VDC |
Min. Load | 5 VDC 2 mA |
Max. Load Resistive | 0.5 A point 0.8 A COM port 0.3 A HSPO point |
Max. Load Inductive | 12 W / 24 VDC 7.2 W HSPO point |
Max. Load Genral | 0.9 W / 24 VDC |
Response Time | <0.2 ms (Pulse output terminal: <5 us) |
CE | YES |
Code | Description |
---|---|
LX3V-0806MR-A2 | PLC, 8 Input, 6 realy output, 1 x RS485, 1 x BD Board |
LX3V-1208MR-A2 | PLC, 12 Input, 8 realy output, 1 x RS485, 1 x BD Board |
LX3V-1212MR-A | PLC, 12 Input, 12 realy output, 2 x RS485, 1 x BD Board, Expandable |
LX3V-1412MR-A | PLC, 14 Input, 12 realy output, 2 x RS485, 1 x BD Board, Expandable |
LX3V-1616MR-A | PLC, 16 Input, 16 realy output, 2 x RS485, 2 x BD Board, Expandable |
LX3V-2416MR-A | PLC, 24 Input, 16 realy output, 2 x RS485, 2 x BD Board, Expandable |
LX3V-2424MR-A | PLC, 24 Input, 24 realy output, 2 x RS485, 2 x BD Board, Expandable |
LX3V-3624MR-A | PLC, 36 Input, 24 realy output, 2 x RS485, 2 x BD Board, Expandable |
Code | Description |
---|---|
LX5S-0806MR-A | PLC, 8 Input, 6 realy output, 1 x RS485, 1 x BD Board |
LX5S-1208MR-A | PLC, 12 Input, 8 realy output, 1 x RS485, 1 x BD Board |
LX5S-1412MR-AN | PLC, 14 Input, 12 realy output, 2 x RS485, 1 x ethernet, 1 x BD Board, Expandable |
LX5S-1616MR-AN | PLC, 16 Input, 16 realy output, 2 x RS485, 1 x ethernet, 2 x BD Board, Expandable |
LX5S-2416MR-AN | PLC, 24 Input, 16 realy output, 2 x RS485, 1 x ethernet, 2 x BD Board, Expandable |
LX5S-2424MR-AN | PLC, 24 Input, 24 realy output, 2 x RS485, 1 x ethernet, 2 x BD Board, Expandable |
LX5S-3624MR-AN | PLC, 36 Input, 24 realy output, 2 x RS485, 1 x ethernet, 2 x BD Board, Expandable |